Local Hmi Functionality; Protection And Alarm Indication - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 5
Local HMI
24
IED status LEDs
5.4

Local HMI functionality

5.4.1

Protection and alarm indication

Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
Table 8:
LED state
Off
On
Flashing
Table 9:
LED state
Off
On
Flashing
Table 10:
LED state
Off
On
Flasing
96
The start and trip LEDs are configured via the disturbance recorder.
The yellow and red status LEDs are configured in the disturbance recorder
function, DRPRDRE, by connecting a start or trip signal from the actual function
to a BxRBDR binary input function block using the PCM600 and configure the
Off , Start or Trip for that particular signal.
setting to
Ready LED (green)
Description
Auxiliary supply voltage is disconnected.
Normal operation.
Internal fault has occurred.
Start LED (yellow)
Description
Normal operation.
A protection function has started and an indication message is displayed.
The start indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the LHMI,
press
The IED is in test mode and protection functions are blocked, or the IEC61850
protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and blocking
is removed. The blocking of functions through the IEC61850 protocol can be
reset in Main menu/Test/Reset IEC61850 Mod. The yellow LED changes to
either On or Off state depending on the state of operation.
Trip LED (red)
Description
Normal operation.
A protection function has tripped. An indication message is displayed if the
auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the LHMI,
press
Configuration mode.
.
.
1MRK 504 152-UEN B
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v15
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents