1MRK 506 369-UEN B
5.4
5.4.1
Line distance protection REL670 2.2 IEC
Application manual
20
Clear
21
Help
22
Communication port
23
Programmable indication LEDs
24
IED status LEDs

Local HMI functionality

Protection and alarm indication
Protection indicators
The protection indicator LEDs are Ready, Start and Trip.
The start and trip LEDs are configured via the disturbance recorder.
The yellow and red status LEDs are configured in the disturbance
recorder function, DRPRDRE, by connecting a start or trip signal
from the actual function to a BxRBDR binary input function block
using the PCM600 and configure the setting to Off, Start or Trip for
that particular signal.
Table 11:
Ready LED (green)
LED state
Description
Off
On
Flashing
Table 12:
Start LED (yellow)
LED state
Description
Off
On
Flashing
Auxiliary supply voltage is disconnected.
Normal operation.
Internal fault has occurred.
Normal operation.
A protection function has started and an indication message is displayed.
The start indication is latching and must be reset via communication,
LHMI or binary input on the LEDGEN component. To open the reset
menu on the LHMI, press
The IED is in test mode and protection functions are blocked, or the
IEC61850 protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and
blocking is removed. The blocking of functions through the IEC61850
protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The
yellow LED changes to either On or Off state depending on the state of
operation.
Section 5
Local HMI
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v16
.
101