Advanced Setup Parameters - Lenze SMV Series Operating Instructions Manual

Table of Contents

Advertisement

4.5.3

Advanced Setup Parameters

Code
No.
Name
Base Voltage
P165
Carrier Frequency
P166
Base Frequency
p167
(1)
Fixed Boost
p168
Accel Boost
p169
Slip Compensation
P170
Current Limit
p171
(1)
Current Limit
P172
Reduction
Decel Override
P173
Time
DC Brake Voltage
P174
DC Brake Time
p175
EDBSV571 EN 1.0
Possible Settings
Default
Selection
15
{V}
0
0 4 kHz
1 6 kHz
2 8 kHz
3 10 kHz
60.0
10.0
{Hz}
0.0
{%}
NOTE
• P167 = rated motor frequency for standard applications
• P165, P168 = default setting depends on drive rating
0.0
0.0
{%}
0.0
0.0
{%}
Max I
30
{%}
0
0 Current Limit Reduction Active -
Normal response
1 Current Limit Reduction Active -
Fast response
2 Current Limit Reduction Disabled
- Normal response
3 Current Limit Reduction Disabled
- Fast response
2.0
0.0
{s}
0.0
0.0
{%}
0.0
0.0
{s}
NOTE: CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P174) is applied for the time specified by P175 with the following
exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a
run or fault condition occurs.
• If P110=2, 4...6 and P175=999.9, brake voltage will be applied for 15s
• If P121...P124=18 and the corresponding TB-13 input is CLOSED, brake voltage will
be applied until the TB-13 input is OPENED or a fault condition occurs.
Commissioning
IMPORTANT
1000
Valid for V/Hz mode only.
Set voltage for bus compensation in V/Hz
mode
• As carrier frequency is increased, motor
noise is decreased
• Observe derating in section 2.3
• Automatic shift to 4 kHz at 120% load
• NEMA 4X (IP65) Models: Default = 0 (4kHz)
• NEMA 1 (IP31) Models: Default = 1 (6kHz)
1500
40.0
20.0
Accel Boost is only active during acceleration
40.0
Increase P170 until the motor speed no
longer changes between no load and full load
conditions.
Max I
• When the limit is reached, the drive
displays CL(Current Limit), and either the
acceleration time increases or the output
frequency decreases.
• Digital outputs can also indicate when the
limit is reached; see P140, P142.
• Refer to section 2.3 for the maximum
output current Max I (%)
In field weakening, the Current Limit is
inversely proportional to the speed.
60.0
Maximum time before drive trips into HF
fault.
50.0
Setting is a percent of the nominal DC bus
voltage.
999.9
EN
V0112
25