Commissioning
4.5
Parameter Menu
4.5.1
Basic Setup Parameters
Code
No.
Name
Start Control
P100
Source
EN
Standard
P101
Reference
Source
Minimum
P102
Frequency
Maximum
p103
Frequency
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the motor/machine
may cause damage to equipment and injury to personnel!
Acceleration
P104
Time 1
Deceleration
P105
Time 1
EXAMPLE: IF P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz; then the rate of frequency change
from 0 Hz to 120 Hz = 40.0 s
S-Ramp
P106
Integration
Time
20
Possible Settings
Default Selection
0
0 Local Keypad
1 Terminal Strip
2 Network Only
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled if parameters
are reset back to defaults (see P199)
NOTE
• The STOP button on the front of the drive is always active except in JOG mode.
• TB-1 is an active STOP input if P100 is set to a value other than 0.
0
0 Keypad (Local or Remote)
1 0-10 VDC
2 4-20 mA
3 Preset #1 (P131)
4 Preset #2 (P132)
5 Preset #3 (P133)
6 Network
7 Preset Sequence Segment #1 (P710) Selections 7, 8 & 9 are not valid for PID
8 Preset Sequence Segment #2 (P715)
9 Preset Sequence Segment #3 (P720)
0.0
0.0
{Hz}
80.0
7.5
{Hz}
NOTE
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows HiFr (flashing).
- Release p button and wait one second.
- Press p button again to continue increasing P103.
30.0
0.0
{s}
30.0
0.0
{s}
0.0
0.0
{s}
IMPORTANT
Use RUN button on front of drive to start
Use start/stop circuit wired into the terminal
strip. Refer to section 3.2.3
• Start command must come from network
(Modbus, CANopen, etc)
• SMV models <15HP (11kW) require optional
communication module (refer to the
network module documentation).
Selects the default speed or torque reference
when no Auto Reference is selected using the
TB-13 input.
setpoint or torque reference.
P103
• P102, P103 are active for all speed references
• When using an analog speed reference, also
see P160, P161
500
3600
• P104 = time of frequency change from 0 Hz
to P167 (base frequency)
• P105 = time of frequency change from
3600
P167 to 0 Hz
• For S-ramp accel/decel, adjust P106
50.0
• P106 = 0.0: Linear accel/decel ramp
• P106 > 0.0: Adjusts S-ramp curve for
smoother ramp
EDBSV571 EN 1.0