Technical Data

2
Technical Data
2.1

Standards and Application Conditions

Conformity
Approvals
Input voltage phase imbalance
Supported Power Systems
EN
Humidity
Temperature range
Installation height
Vibration resistance
Earth leakage current
Max Permissable Cable Length
Enclosure
Protection measures against
Compliance with EN 61000-3-2
Requirements
(2)
Compliance with EN 61000-3-12
Requirements
(2)
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic
Compatibility (EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/
phase).
(1) The stated cable lengths are permissible at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN
61000-3-2.
The machine/system manufacturer is responsible for the machine's compliance with the regulations.
6
CE
Low Voltage (2006/95/EC) & EMC (2004/108/EC) Directives
UL508C
Underwriters Laboratories -Power Conversion Equipment
< 2%
− For central grounded systems, operation is permitted
TT
− For corner grounded 400/500V systems, operation is
TN
< 95% non-condensing
Transport
-25 ... +70°C
Storage
-20 ... +70°C
Operation
-10 ... +55°C (with 2.5%/°C current derating above +40°C)
0 - 4000m a.m.s.l.
(with 5%/1000 m current derating above 1000m a.m.s.l.)
acceleration resistant up to 1.0g
> 3.5 mA to PE
<= 4.0 Hp (3.0 kW)
30 meters shielded, 60 meters un-shielded
(1)
=> 5.0 Hp (3.7 kW)
50 meters shielded, 100 meters un-shielded.
IP31/NEMA 1
IP65/NEMA 4X
NEMA 1 and NEMA 4X model enclosures are plenun rated in accordance with UL
508C and are suitable for installation in a compartment handling conditioned air.
short circuit, earth fault, phase loss, over voltage, under voltage,
motor stalling, over temperature, motor overload
< 0.5kW
with mains choke
0.5 ... 1kW
with active filter
> 1kW
without additional measures
Additional measures required for compliance with EN 61000-
16 ... 75amp
3-12
without restrictions.
possible but reinforced insulation to control circuits is
compromised.
EDBSV571 EN 1.0