Drive Configuration Messages

When the Mode button is pressed and held, the drive's display will provide a 4-digit code that indicates how
the drive is configured. If the drive is in a Stop state when this is done, the display will also indicate which
control source commanded the drive to Stop (the two displays will alternate every second).
Format = x.y.zz
x = Control Source:
L
= Local Keypad
t
= Terminal Strip
r
= Remote Keypad
n
= Network
Example:
L.S.CP
t.p.EU
t.C.12
n.t.p2
n.S.03
.StP
L.stp
Format = x
t.stp
r.stp
n.stp
EDBSV571 EN 1.0
Troubleshooting and Diagnostics
Configuration Display
y = Mode:
S
= Speed mode
P
= PID mode
t
= Torque mode
C
= Sequencer mode
= Local Keypad Start control, Speed mode, Keypad speed reference
= Terminal Strip Start control, PID mode, 0-10 VDC setpoint reference
= Terminal Strip Start control, Sequencer Operation (Speed mode), Segment #12
= Network Start control, Vector Torque mode, Preset Torque #2 reference
= Network Start control, Speed mode, Speed reference from Sequencer segment #03
Stop Source Display
= Stop command came from Local Keypad
= Stop command came from Terminal Strip
= Stop command came from Remote Keypad
= Stop command came from Network
zz = Reference:
CP
= Keypad p q
EU
= 0-10 VDC (TB-5)
E1
= 4-20 mA (TB-25)
JG
= Jog
nt
= Network
OP
= MOP
P1...P7
= Preset 1...7
01...16
= Sequencer Segment