Code
No.
Name
Preset Torque
P334
Setpoint #4
(2)
Current Loop P
P340
(1)
Gain
Current Loop I Gain
(1)
P341
Speed Loop Adjust
(1)
P342
Slip Compensation
P343
Response Filter
Motor Auto-
P399
calibration
EDBSV571 EN 1.0
Possible Settings
Default
Selection
100
0
{%}
0.25
0.00
65
12
{ms}
0.0
0.0
{%}
99
90
{ms}
0
0 Calibration Not Done
1 Standard Calibration Enabled
2 Advanced Calibration Enabled
3 Bypass Calibration, enable
operation in vector mode w/o
Auto Calibration
4 Standard Calibration Complete
5 Advanced Calibration Complete
NOTE: To run the Auto Calibration:
− Set P302...P306 according to motor nameplate
− Set P399 = 1 or 2 (if option 1 failed or in case of non-standard motor)
− Make sure motor is cold (20° - 25° C)
− Apply a Start command
− Display will indicate CAL for about 40 seconds
− Once the calibration is complete, the display will indicate Stop; apply another
Start command to actually start the motor
− Parameter P399 will now be set to 4 or 5.
Commissioning
IMPORTANT
400
TB-13D activated; P124 = 3 and P300 = 5
16.0
Changing these settings can adversely affect
performance. Contact factory technical support
prior to changing.
9990
20.0
9999
Low pass filter time constant for varying the
slip compensation response to changes in the
motor current.
• If P300 = 4 or 5, motor calibration must be
performed if P399 is not set to 3 (bypass
calibration).
• If P300=2 or 3, motor calibration is
recommended.
• Use option 2 if option 1 failed or in case of
non-standard motors
• An alternating CAL / Err will occur if:
- attempt motor calibration with P300 = 0 or 1
- motor calibration is attempted before
programming motor data
EN
31