Commissioning
Code
No.
Name
Start Method
P110
EN
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/
restarting should only be used on equipment that is inaccessible to personnel.
Stop Method
P111
Rotation
P112
22
Possible Settings
Default Selection
3
0 Normal
1 Start on Power-up
2 Start with DC Brake
3 Auto Restart
4 Auto Restart with DC Brake
5 Flying Start/Restart - Type 1
6 Flying Start/Restart - Type 1
7 Flying Start /Restart - Type 2
for 2-pole motors requiring a flying
restart
8 Flying Start/Restart - Type 2
for 2-pole motors requiring a flying
restart
NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up; F.UF
fault will occur if start command is applied too soon.
• P110 = 1, 3...6: For automatic start/restart, the start source must be the terminal strip
and the start command must be present.
• P110 = 2, 4...6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3...6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays LC
(fault lockout) and requires manual reset.
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into
• P110 = 5, 6: If drive trips into
0
0 Coast
1 Coast with DC Brake
2 Ramp
3 Ramp with DC Brake
1
0 Forward Only
1 Forward and Reverse
IMPORTANT
Drive will automatically start when power
is applied.
When start command is applied, drive will
apply DC braking according to P174, P175
prior to starting the motor
Drive will automatically restart after faults, or
when power is applied.
Combines settings 2 and 3
• Drive will automatically restart after faults,
or when power is applied.
• After 3 failed attempts, drive will Auto
Restart with DC brake.
• P110 = 5, 7: Performs speed search, starting
at Max Frequency (P103)
• P110 = 6, 8: Performs speed search, starting
at the last output frequency prior to faulting
or power loss
• If P111 = 0, a flying START is performed when
a start command is applied.
• P110 = 7,8: Utilizes P280/281 to set Max
Current Level and Decel Time for restart
F
OF
.
fault, try P110 = 7 or 8.
Drive's output will shut off immediately upon
a stop command, allowing the motor to coast
to a stop
The drive's output will shut off and then the
DC Brake will activate (refer to P174, P175)
The drive will ramp the motor to a stop
according to P105 or P126.
The drive will ramp the motor to 0 Hz and
then the DC Brake will activate (refer to P174,
P175)
If PID mode is enabled, reverse direction is
disabled (except for Jog).
F
rF
.
fault.
EDBSV571 EN 1.0