Fuses/Cable Cross-Sections - Lenze SMV Series Operating Instructions Manual

Table of Contents

Advertisement

3.2.2

Fuses/Cable Cross-Sections

NOTE: Observe local regulations. Local codes may supersede these recommendations
WARNING: Per UL, use a FUSE for 240V drives requiring >40A protection and for 400/480/600V drives requiring >32A protection.
Type
ESV251N01SXB
120V
ESV371N01SXB
1~
ESV751N01SXB
(1/N/PE)
ESV112N01SXB
ESV251N01SXB, ESV251N02SXB,
ESV371N01SXB, ESV371N02YXB
ESV751N01SXB, ESV751N02YXB
240V
1~
ESV112N02YXB, ESV112N01SXB
(2/PE)
ESV152N02YXB
ESV222N02YXB
ESV371N02YXB, ESV751N02YXB
ESV112N02YXB, ESV152N02YXB,
ESV112N02TXB, ESV152N02TXB
ESV222N02YXB, ESV222N02TXB
240V
ESV402N02TXB
3~
(3/PE)
ESV552N02TXB
ESV752N02TXB
ESV113N02TXB
ESV153N02TXB
ESV371N04TXB ...ESV222N04TXB
ESV402N04TXB
ESV552N04TXB
400V
ESV752N04TXB
or 480V
ESV113N04TXB
3~(3/PE)
ESV153N04TXB
ESV183N04TXB
ESV223N04TXB
ESV751N06TXB ...ESV222N06TXB
ESV402N06TXB
ESV552N06TXB
ESV752N06TXB
600V
3~(3/PE)
ESV113N06TXB
ESV153N06TXB
ESV183N06TXB
ESV223N06TXB
Notes for Fuse and Cable Table:
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.
(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.
(3) Thermomagnetic type breakers preferred.
Observe the following when using Ground Fault Circuit Interrupters (GFCIs):
• Installation of GFCI only between supplying mains and controller.
• The GFCI can be activated by:
- capacitive leakage currents between the cable screens during operation (especially with long, screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters
EDBSV571 EN 1.0
Recommendations
Miniature
Fuse
Fuse
circuit
North America
breaker
(1)
M10 A
C10 A
10 A
M16 A
C16 A
15 A
M25 A
C25 A
25 A
M32 A
C32 A
30A
M10 A
C10 A
10 A
M16 A
C16 A
15 A
M20 A
C20 A
20 A
M25 A
C25 A
25 A
M32 A
C32A
30 A
M10 A
C10 A
10 A
M16 A
C16 A
12 A
M20 A
C20 A
20 A
M32 A
C32 A
30 A
M40 A
C40 A
35 A
M50 A
C50 A
45 A
M80 A
C80 A
80 A
M100 A
C100 A
90 A
M10 A
C10 A
10 A
M16 A
C16 A
20 A
M20 A
C20 A
20 A
M25 A
C25 A
25 A
M40 A
C40 A
40 A
M50 A
C50 A
50 A
M63 A
C63A
70 A
M80 A
C80 A
80 A
M10 A
C10 A
10 A
M16 A
C16 A
12 A
M16 A
C16 A
15 A
M20 A
C20 A
20 A
M32 A
C32 A
30 A
M40 A
C40 A
40 A
M50 A
C50 A
50 A
M63 A
C63 A
60 A
Installation
Input Power Wiring
Breaker
(2)
(3)
(L1, L2, L3, PE)
[mm²]
[AWG]
10 A
1.5
15 A
2.5
25 A
4
30A
4
10 A
1.5
15 A
2.5
20 A
2.5
25 A
2.5
30 A
4
10 A
1.5
12 A
1.5
20 A
2.5
30 A
4.0
35 A
6.0
10
16
16
10 A
1.5
20 A
2.5
20 A
2.5
25 A
4.0
4
10
10
16
10 A
1.5
12 A
1.5
15 A
2.5
20 A
2.5
30 A
4
4
6
10
14
14
EN
10
10
14
14
12
12
10
14
14
12
10
8
8
6
4
14
14
14
10
8
8
6
6
14
14
14
12
10
8
8
8
15