Code
No.
Name
Preset PID Setpoint
P232
#2
Preset PID Setpoint
P233
#3
Preset PID Setpoint
P234
(2)
#4
Sleep Threshold
P240
Sleep Delay
P241
Sleep Bandwidth
P242
Feedback Sleep
P243
Entry Threshold
Sleep Entry Mode
P244
Sleep Entry Stop
P245
Type
Feedback Recovery
P246
from Sleep
Threshold
Sleep Recovery
P247
Mode
Auto Rinse in Sleep
P250
Mode
Time Delay
P251
between Auto
Rinses
Auto Rinse Speed
P252
Auto Rinse Time
P253
Current Level:
P280
Flying Restart
Type 2
Decel Time: Flying
P281
Restart Type 2
EDBSV571 EN 1.0
Possible Settings
Default
Selection
0.0
P204
0.0
P204
0.0
P204
0.0
0.0
{Hz}
30.0
0.0
{s}
0.0
0.0
Where: B
= |(P205 - P204)|
max
0.0
P204
0
0 Enter SLEEP if Drive Speed <P240
1 Enter SLEEP if Feedback >P243
2 Enter SLEEP if Feedback <P243
0
0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
0.0
P204
0
0 Recovery if Speed Setpoint > P240
or if PID feedback differs from
setpoint by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
0
0 Disabled
1 Enabled
30.0
0.0
{min}
0.0
-500.0
{Hz}
0.0
0.0
{sec}
Auto Pump Rinse Setup:
P250=1 (Enabled)
P251=# minutes between each Pump
Rinse
P252=Hz speed of Pump Rinse
P253=# seconds Pump Rinse duration
70.0
0.0
{%}
3.0
0.0
{sec}
Commissioning
IMPORTANT
P205
TB-13B activated; P122 = 3 and P200 = 1 or 2
P205
TB-13C activated; P123 = 3 and P200 = 1 or 2
P205
TB-13D activated; P124 = 3 and P200 = 1 or 2
500.0
• If drive speed < P240 for longer than
P241, output frequency = 0.0 Hz; drive
300.0
display = SLP
B
• P240 = 0.0: Sleep mode is disabled.
max
• P200 = 0...2: Drive will start again when
speed command is above P240
• P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242 or when the PID
loop requires a speed above P240.
P205
Active only when P244 = 1 or 2
For time longer than P241
For time longer than P241 or same as Sel 0
For time longer than P241 or same as Sel 0
P205
Active only when P247 = 1 or 2
Activated in sleep mode only.
Sleep Recovery cancels Auto Rinse
6553.5
Time delay reset by re/entering sleep mode
500.0
If P112 = 1, negative sign = reverse direction
6553.5
Does not include time to decel back to speed
P104/
P125
Delay Time
between each
Pump Rinse
P251
P171
Maximum current during Type 2 flying restart
operation
3600.0
Deceleration rate used during Type 2 flying
restart operation
Pump Rinse Speed
P252
P105/
P126
Pump Rinse Time
P253
Time
29
EN