Commissioning
Code
No.
Name
Keypad Setpoint
p176
Single Press
Increment
Display Frequency
p178
Multiplier
Run Screen Display
p179
EN
Oscillation
p180
Damping Control
Skip frequency 1
p181
Skip frequency 2
p182
Skip frequency
p184
bandwidth
Voltage Midpoint
p185
V/Hz characteristic
Frequency
(2)
p187
Midpoint V/Hz
characteristic
Motor Braking
p190
Motor Brake Level
p191
26
Possible Settings
Default
Selection
0.1
0.1
0.00
0.00
EXAMPLE
If
P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)
0
0
{Parameter Number}
0
0
0.0
0.0
{Hz}
0.0
0.0
{Hz}
0.0
0.0
{Hz}
NOTE
Bandwidth (Hz) = f
(Hz) + P184 (Hz)
s
EXAMPLE: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
0
0.0
{V}
0.0
0.0
{Hz}
0 Disabled
1 Braking with BUS threshold
2 Braking always on with
deceleration
3 Braking with bus regulator
4 Special
WARNING
Flux braking can cause heat in the motor. To avoid damage to the motor, use a PTC
to protect the motor. If the flux brake is used too frequently, the drive will trip fault
"F_PF".
0
0
{%}
(flux
braking
disabled)
IMPORTANT
100.0
Used for run screen setpoint editing only.
If P176 >0.1 then scrolling of keypad setpoint
is enabled.
650.00
• Allows frequency display to be scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency
X P178
599
• 0 = Normal Run Screen, this display depends
on mode of operation. Refer to section 4.2.
• Other selections choose a diagnostic
parameter to display (P501...P599).
• Parameters P560 - P564 are selectable
if the sequencer is enabled (P700 is not
0). P560-P564 are not visible until P700
is enabled.
80
0 = Damping disabled
Compensation for resonances within drive
500
• Drive will not run in the defined skip range;
used to skip over frequencies that cause
500
mechanical vibration
10.0
• P181 and P182 define the start of the
skip ranges
• P184 > 0 defines the bandwidth of both
ranges.
f
= P181 or P182
s
P165
Valid only when P300 = 0 or 2.
Use with P187 to define midpoint on V/Hz
curve.
P167
Valid only when P300 = 0 or 2.
Use with P185 to define midpoint on V/Hz
curve.
Flux brake OFF.
When drive is in deceleration and V
V
(114% of the rated V
deceleration freeze
brake will be turned ON.
As long as drive is in deceleration, the flux
brake will be ON.
When drive is in deceleration and V
(114% of the rated V
freeze
increased to reduce the bus voltage. Determined by
the value in P191, the speed increment = slip speed *
P191(%) / 37.
(Consult factory before using)
75
Active when P190 > 0 and drive is in deceleration
mode. Use to reduce deceleration time on high
inertia loads.
NOTE: Over usage of P190 can cause frequent
'overload' trips "F.PF"
Not active for P300 = 5 (Torque mode)
>
bus
), the flux
bus
> V
bus
deceleration
), the motor speed will be
bus
EDBSV571 EN 1.0