Residential dry pipe system

Advertisement

Quick Links

RAPID RESPONSE
Residential Dry Pipe System
General
Description
The TYCO RAPID RESPONSE Resi-
dential Dry Pipe System provides a
normally dry system for areas subject
to freezing or areas that may be inad-
vertently subject to freezing.
The key components of the RAPID
RESPONSE Residential Dry Pipe
System are:
• Model RCP-1 Residential Control
Panel
• RAPID RESPONSE Residential
Sprinklers specifically Listed for use
in residential dry pipe systems (ver-
sus being limited to wet pipe sys-
tems only)
• TYCO CPVC Pipe and Fittings made
with BLAZEMASTER Compound
• SprinkFDT Fluid Delivery Calculation
Software
Typically, residential sprinklers based
on their Listing are limited to wet pipe
sprinkler systems to assure speed of
water delivery for a prescribed design
area (the number of design sprinklers).
The Model RCP-1 Residential Control
Panel, in combination with specific
Rapid Response Residential Sprin-
klers listed for use in dry pipe systems,
provides options for areas sensitive to
freezing.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 14
To achieve UL Listing, the RAPID
RESPONSE Residential Sprinklers
have undergone rigorous testing to
meet UL1626 fire test criteria, includ-
ing a 15-second delay for water deliv-
ery as required for residential sprinklers
intended for use in dry pipe systems.
NOTICE
The RAPID RESPONSE Residential Dry
Pipe System described herein must be
installed and maintained by qualified
personnel in compliance with this docu-
ment, and with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the requirements of any other authori-
ties having jurisdiction. Failure to do
so may impair the performance of this
device.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition
and in compliance with all applicable
standards and requirements. Contact
the installing contractor or product
manufacturer with any questions.
Do not disconnect batteries or turn off
AC power to quiet unwanted alarms.
The Model RCP-1 Panel will not operate
(that is, release water or energize
alarms) if AC power is not connected,
has failed, or has been interrupted
for any reason and the battery is dis-
connected, drained, or improperly
connected.
The use of an automatic sprinkler
system does not allow for omission of a
Household Fire Alarm System installed
per NFPA 72. The Model RCP-1 Panel
is not intended to be used as part of a
Household Fire Alarm System.
Disconnect electrical field power when
making any internal adjustments or
repairs. Failure to do so may result in
personal injury. Servicing should be
performed by qualified personnel.
Static electricity can damage com-
ponents. Therefore, qualified person-
nel must be grounded before opening
components, installing components,
and prior to installation. Keep compo-
nents wrapped in anti-static material at
all times.
FEBRUARY 2019
Worldwide
www.tyco-fire.com
Contacts
TFP485

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls tyco RAPID RESPONSE RCP-1

  • Page 1 Worldwide www.tyco-fire.com Contacts RAPID RESPONSE Residential Dry Pipe System General To achieve UL Listing, the RAPID RESPONSE Residential Sprinklers Description have undergone rigorous testing to meet UL1626 fire test criteria, includ- ing a 15-second delay for water deliv- The TYCO RAPID RESPONSE Resi- ery as required for residential sprinklers dential Dry Pipe System provides a intended for use in dry pipe systems.
  • Page 2: Technical Data

    TFP485 Page 2 of 14 Technical This equipment generates, uses, and The Model RCP-1 Panel includes the can radiate radio frequency energy, following features: Data and if not installed and used in accor- • Pre-wired assembly containing pre- dance with this technical data sheet, programmed control panel, sys- may cause interference to radio com- tem performance gauges, and an...
  • Page 3 TFP485 Page 3 of 14 Design To facilitate draining, piping in areas NOTICE subject to freezing shall be pitched in In no case shall the time of water deliv- Criteria accordance with NFPA 13D for dry pipe ery exceed 15 seconds for the most systems.
  • Page 4 TFP485 Page 4 of 14 Specifications • Living Space: 1870 sq. ft • Air Temperature: 0°F • Pipe & Fittings: 1 in. CPVC • System Volume: 8.6 gal • Sprinklers: Horizontal Sidewall TY1334, K=4.2 • Coverage Area: 14 ft x 14 ft •...
  • Page 5 TFP485 Page 5 of 14 Specifications • Living Space: 3480 sq. ft • Air Temperature: 0°F • Pipe & Fittings: 1 in. CPVC • System Volume: 18.6 gal • Sprinklers: Pendent TY2235, K=4.9 • Coverage Area: 16 ft x 16 ft •...
  • Page 6 TFP485 Page 6 of 14 8" 14" (200 mm) (355 mm) 1-3/4" 2-7/8" ELECTRONIC (45 mm) (73 mm) CONTROL 5" OPERATOR BACKUP (127 mm) INTERFACE BATTERIES OPERATOR WINDOW INTERFACE PRESSURE CONTROL DISCONNECT "ON/OFF" SWITCH OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM SYSTEM...
  • Page 7 TFP485 Page 7 of 14 Steel Pipe CPVC and Copper Pipe (Internally Galvanized for Residential Dry Pipe Systems) Potable Non-Potable Potable Non-Potable Water Water Water Water Residential Residential Ambient Ambient Ambient Ambient Sprinkler Sprinkler Temperature Temperature Temperature Temperature Type Type <...
  • Page 8 TFP485 Page 8 of 14 DRY PIPE Minimum Flow Maximum Maximum Residual Pressure for Horizontal Ceiling Coverage Area Spacing (Maximum 2 in. Rise for 12 in. Run) ft x ft (m x m) 155°F 175°F (68°C) (79°C) 12 x 12 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) (3,7 x 3,7)
  • Page 9 TFP485 Page 9 of 14 DRY PIPE Minimum Flow and Residual Pressure for Horizontal Ceilings Maximum Maximum (Maximim 2 in. Rise for 12 in. Run) Coverage Area Spacing ft x ft Recessed Pendent (m x m) (TY2235) 155°F (68°C) 12 x 12 13 GPM (49,2 LPM) (3,7 x 3,7) (3,7)
  • Page 10: Operator Interface

    TFP485 Page 10 of 14 ELEVATION DRY PIPE Minimum Flow and Residual Pressure Maximum Maximum Coverage Area Spacing Top-of-Deflector to Ceiling: Top-of-Deflector to Ceiling: Width x Length 4 to 6 in. (100 to 150 mm) 6 to 12 in. (100 to 150 mm) ft x ft (m x m) 155°F...
  • Page 11: Operation

    TFP485 Page 11 of 14 • SYSTEM RELEASED Panel Reference Name Description The red SYSTEM RELEASED LED turns on steady when the RAC cir- Initiating Device Circuit Low Air Pressure cuit is activated. Activation of the RAC circuit energizes the Solenoid Notification Appliance Circuit Optional Notification Appliance Valve to permit water to enter the...
  • Page 12: Alarm Condition

    TFP485 Page 12 of 14 In Case of Step 2. Silence alarms by pressing the wire insulation, can damage the pipe SIGNAL SILENCE key. and fittings through contact resulting Supervisory/ in damage/failure to the system. Step 3. Close the Main Control Valve. Care and Trouble Step 4.
  • Page 13 TFP485 Page 13 of 14 INTERFACE PROGRAM SYSTEM PROGRAMMING MODE CARD SWITCH MODE 1 POSITION 1 MODE 2 POSITION 2 MODE 3 POSITION 3 MODE 4 POSITION 4 MODE 5 POSITION 5 MODE 6 POSITION 6 MODE 7 POSITION 7 MODE 8 POSITION 8 MODE 9...
  • Page 14: Limited Warranty

    1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...

Table of Contents