Johnson Controls P2000 Hardware Installation

Security management system
Hide thumbs Also See for P2000:

Advertisement

Quick Links

P2000
Security Management System
hardware
installation
CKM-MR16OUT
authentic Mercury™ terminal module
24-10707-82 Revision D
December 2017

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls P2000

  • Page 1 P2000 Security Management System hardware installation CKM-MR16OUT authentic Mercury™ terminal module 24-10707-82 Revision D December 2017...
  • Page 2 If this document is translated from the original English version by Johnson Controls, all reasonable endeavors will be used to ensure the accuracy of translation. Johnson Controls shall not be liable for any translation errors contained herein or for incidental or consequential damages in connection with the furnishing or use of this translated material.
  • Page 3 Declarations of Conformity United States: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 4 UNDERWRITERS LABORATORIES COMPLIANCE VERIFICATION SHEET The following model number is listed under Underwriters Laboratories® (UL) 1076 for Proprietary Burglar Alarm Units and Systems, UL 294 for Access Control Systems Units and Underwriters Laboratories of Canada ULC/ORD-C1076-86. CKM-MR16OUT When installed at the site the following requirements must be met to comply with these standards. 1.
  • Page 5: General Information

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D CKM-MR16OUT T ERMINAL ODULE This document provides hardware installation and setup instructions for CKM-MR16OUT, the authentic Mercury™ terminal module. This document is divided into the following sections: • General Information on page 1 •...
  • Page 6: Wiring Information

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D OUNTING NFORMATION RELAY STATUS LEDs 6.00 [152.40] .25 [6.35] 5.50 [139.70] 10 11 13 14 OUT 9 OUT 1 OUTPUTS OUT 10 OUT 2 OUT 11 OUT 3 OUT 4 OUT 12 OUTPUTS OUT 13 OUT 5 OUT 14...
  • Page 7: Supplying Power

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Cable Routing The cables should run in grounded conduit or at least two feet from AC power, fluorescent lights, or other high energy sources. : All data cables should be physically separated from power lines. If MPORTANT conduit is used, do not run data cables in the same conduit as power cables or certain door strike cables, e.g.
  • Page 8 CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Communications Wiring The CKM-MR16OUT communicates to a controller via a two-wire RS- 485 interface. The interface allows multidrop communication on a single bus of up to 4,000 feet (1,200 m). Use twisted pair (minimum 24 AWG) with shield for the communication line.
  • Page 9: Setup Information

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Relay Outputs Wiring The following diagrams show typical use of the relay. A DC power source is recommended whenever possible. Transient clamping must be provided to protect the contacts and to reduce EMI emission. Use sufficiently large wires for the load current to avoid voltage loss.
  • Page 10 CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Table 2: Switches Selection OFF OFF OFF OFF OFF Address 0 OFF OFF OFF OFF ON Address 1 OFF OFF OFF ON OFF Address 2 OFF OFF OFF ON Address 3 OFF OFF ON OFF OFF Address 4 OFF OFF ON OFF ON...
  • Page 11: Status Leds

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Table 2: Switches Selection OFF ON Address 29 OFF Address 30 Address 31 OFF OFF 115,200 BPS OFF ON 9,600 BPS 19200 BPS 38,400 BPS Encrypted communication not required Encrypted communication required 1. Firmware revisions prior to 1.38.1, this setting is 2,400 BPS. 2.
  • Page 12: Specifications

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Table 3: LED Information Process LED Information Running A LED Error Indication: (continued) Waiting for application firmware to be downloaded: 1 second ON 1 second OFF Running B LED SIO Communication Port Status: (continued) Indicates communication activity on the SIO communication port.
  • Page 13: Maintenance

    CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D Table 4: CKM-MR16OUT Specifications Category Description Mechanical Dimensions 6 in x 8 in x 1in (152mm x 203 mm x 25 mm) (W x L x H) Weight 14 oz. (400 g) nominal AINTENANCE Impaired Performance The following is a list of the impaired performance conditions:...
  • Page 14 CKM-MR16OUT Hardware Installation Manual 24-10707-82 Rev. D...
  • Page 15 Security Solutions (805) 522-5555 www.johnsoncontrols.com We welcome your comments at BE-techpubs-security@jci.com.