Overview Of Auma Electrical Connections - AUMA SA Series Operating Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SA Series:
Table of Contents

Advertisement

SA 07.2
SA 16.2 / SAR 07.2
AC 01.2 Non-Intrusive EtherNet/IP
Cable installation in ac-
cordance with EMC
Network cables
5.2.

Overview of AUMA electrical connections

SAR 16.2 Control unit: electronic (MWG)
Network cables are sensitive to interference. Motor cables are interference sources.
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
The interference immunity of network cables increases if the cables are laid
close to the earth potential.
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
This device is equipped with a network port.
Table 16:
Cable recommendation
Only network cables suitable for Industrial Ethernet are to be used.
Minimum requirement
Cable recommendation
Prior to installation, please note:
Install network cables at a distance of minimum 20 cm to other cables.
If possible, network cables should be laid in a separate, conductive, and earthed
cable tray.
Ensure absence of equipotential earth bonding differences between the indi-
vidual devices within the network (perform an equipotential earth bonding).
Do not use network hubs.
Table 17: Transmission rate/cable length for star topology or point-to-point wiring
Baud rate (kbit/s)
Maximum cable length: between two network participants for copper cables
10/100 Mbits/s
100 m
The section below provides an overview of the different electrical connections
described in the chapters to follow.
Table 18: Versions of the AUMA plug/socket connector
Electrical con-
Figure
nection
SJ
Compact version
SF
Cat.5e for fixed installation, 2x2xAWG22 structure
Cat.6e for fixed installation, 2x2xAWG22 structure
Properties
Plug/socket connector with enlarged
terminal compartment
Plug/socket connector with remov-
able cover and enlarged terminal
compartment for EtherNet/IP
Electrical connection
For description
and assembly
refer to chapter
page 26, SJ
electrical connec-
tion (AUMA
plug/socket con-
nector)
page 32, Com-
pact version SF
electrical connec-
tion for Ether-
Net/IP
25