Electrical connection
Protection via thermal mo-
tor protection
Safety standards Safety measures and safety equipment must comply with the respectively valid na-
Connecting cables, cable
glands, reducers, blanking
plugs

6.2 Overview of AUMA electrical connections

22
The current value for sizing the protection is derived from the current consumption of
the motor (refer to
Name plate
We recommend adapting the switchgear sizing to the max. current (I
and setting the overcurrent protection device in compliance with the indications in the
electrical data sheet.
Version with thermoswitches as motor protection:
According to EN 60079-14, a thermal overcurrent protection device (e.g. motor
protection switch) must be installed for explosion-proof actuators in addition to the
thermoswitches.
Version with PTC thermistor:
PTC thermistors additionally require a suitable tripping device in the actuator con-
trols.
tional on site specifications. All externally connected devices shall comply with the rel-
evant safety standards applicable for the place of installation.
We recommend using connecting cables and connecting terminals according to
nominal current (I
). (Refer to
N
For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
Use connecting cables, cable glands, reducers, blanking plugs with a minimum
temperature range of +80 °C.
To avoid contact corrosion, we recommend the use of sealing agents for cable
glands and blanking plugs made of metal.
For connecting cables exposed to UV radiation (outdoor installation), use UV res-
istant cables.
For the connection of position transmitters, screened cables must be used.
The section below provides an overview of the different electrical connections de-
scribed in the chapters to follow.
Table 9: Versions of the AUMA plug/socket connector
Electrical connec-
Figure
tion
KT
KES
[} 9]).
Name plate [} 9]
or electrical data sheet.)
Properties
For description and assembly refer to
chapter
Plug-in integral terminal
connection with enlarged
KT/KM electrical connection [} 23]
terminal compartment
Plug-in terminal connec-
tion with enlarged terminal
KES electrical connection [} 28]
compartment