AUMA SA Series Operating Instructions Manual page 76

Multi-turn actuators
Hide thumbs Also See for SA Series:
Table of Contents

Advertisement

Corrective action
Warnings and Out of specification
Indication on display
PVST abort
Wrn no reaction
Torque wrn OPEN
Torque wrn CLOSE
1)
SIL fault
PVST required
Maintenance required
2)
FQM fail safe fault
1)
For actuators controls in SIL version
2)
For actuators with fail safe unit
Table 34:
Faults and Failure
Indication on display
Configuration error
Config. error REMOTE
Internal error
Torque fault CLOSE
Torque fault OPEN
Phase fault
Incorrect phase seq
76
SA 07.2
SA 16.2 / SAR 07.2
Description/cause
Partial Valve Stroke Test (PVST) was aborted or
could not be started.
No actuator reaction to operation commands within
the set reaction time.
Limit value for torque warning in direction OPEN
exceeded.
Limit value for torque warning in direction CLOSE
exceeded.
SIL sub-assembly fault has occurred.
Execution of PVST (Partial Valve Stroke Tests) is
required.
Maintenance is required.
FQM fault
Description/cause
Collective signal 11:
Configuration error has occurred.
Collective signal 22:
Configuration error has occurred.
Collective signal 14:
Internal error has occurred.
Torque fault in direction CLOSE
Torque fault in direction OPEN
When connecting to a 3-ph AC system and with
internal 24 V DC supply of the electronics:
Phase 2 is missing.
When connecting to a 3-ph or 1-ph AC system
and with external 24 V DC supply of the elec-
tronics: One of the phases L1, L2 or L3 is
missing.
The phase conductors L1, L2 and L3 are connected
in the wrong sequence.
Only applicable if connected to a 3-ph AC system.
SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive EtherNet/IP
Remedy
Perform RESET or restart PVST.
Check movement at actuator.
Check parameter Reaction time M0634.
Check parameter Wrn torque OPEN M0768, re-set
if required.
Check parameter Wrn torque CLOSE M0769, re-
set if required.
Refer to separate Manual Functional Safety.
Checking and fault remedy are required. Refer to
FQM operation instructions.
Remedy
Details to display a list of indi-
Press push button
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
AUMA service
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
Manual (Operation and setting).
Perform one of the following measures:
Issue operation command in direction OPEN.
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
Execute reset command via fieldbus.
Perform one of the following measures:
Issue operation command in direction CLOSE.
Set selector switch to position Local control
(LOCAL) and reset fault indication via push
button RESET.
Execute reset command via fieldbus.
Test/connect phases.
Correct the sequence of the phase conductors L1,
L2 and L3 by exchanging two phases.