10 •
750-479 [2 AI DC ±10 V, Differential Measurement Input]

Technical Data

2.1.1.5
Technical Data
Module Specific Data
Number of outputs
Measured-value acquisition
Voltage supply
Current consumption
Signal voltage
Overrange/
measuring range underflow
Input filter
Internal resistance
Resolution of the A/D converter
Monotonicity without missing codes
Resolution of the measured value
Value of a LSB
(Least Significant Bit)
Measuring error
Temperature coefficient
Measuring error
Crosstalk attenuation
Sampling time of repetition
Sampling delay (module)
Sampling delay (channel/channel)
Sampling duration
Method of conversion
Operating mode
Protection
Admissible continuous overload
Voltage resistance
Bit width
DimensionsW x H* x L
* from upper edge of 35 DIN rail
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
EMC-Emission of interference (CE)
2, electrically isolated from each other
time synchronous
via system voltage DC/DC
(internal)
80 mA
typ.
±10 V
status byte and LED
low pass first order, fG = 5 kHz
1 MΩ
14 bit
yes
13 bit + sign bit
1.2 mV
≤ ±0.05% of the full scale value
25 °C
< ±0.01%/K of the full scale value
≤ 0.4 % over whole temperature range
≤ 0.1 % of upper range value (non-linearity)
≥ 80 db
1 ms
1 ms
≤ 1 µs
≤ 5 µs
SAR (Successive Approximation Register)
continuously sampling (preset)
RC circuit
230 V
DC 500V (channel/channel or channel/system)
2 x 16 bits data
2 x 8 bits control/status (option)
12 mm x 64 mm x 100 mm
ca. 55 g
acc. to EN 50082-2 (96)
acc. to EN 50081-1 (93)
WAGO-I/O-SYSTEM 750
I/O Modules

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-479

Table of Contents