750-479/000-001 [2 AI DC ±10 V Differential Measurement Input/Sync]

Process Image

2.1.2.6
Process Image
The analog input module 750-479/000-001 transmits 16-bit measured values
per channel with status information as well as 8 optional status bits to the
coupler/controller.
However, accessing the status byte depends on the fieldbus system being used.
Attention
The representation of the process data of some I/O modules or their
variations in the process image depends on the fieldbus coupler/-controller
used. Please take this information as well as the particular design of the
respective control/status bytes from the section "Fieldbus Specific Design of
the Process Data" included in the description concerning the process image
of the corresponding coupler/controller.
The status information of the 16-bit value is mapped in bit 0 and bit 1, the
digitalized measured value in bit 2 to bit 15.
1)
Process values of module 750-479/000-001
Input voltage
numerical value with status informations
±10 V
>10.0
'0111.1111.1111.11 01'
10.0
'0111.1111.1111.11 00'
7.5
'0110.0000.0000.00 00'
5.0
'0100.0000.0000.00 00'
2.5
'0010.0000.0000.00 00'
0.0
'0000.0000.0000.00 00'
-2.5
'1110.0000.0000.00 00'
-5.0
'1100.0000.0000.00 00'
-7.5
'1010.0000.0000.00 00'
-10.0
'1000.0000.0000.00 00'
<-10.0
'1000.0000.0000.00 01'
status informations: F: Error, Ü: over control
1)
binary
1)
status-
byte
hex.
dec.
hex.
0x7FFD
32765
0x42
0x7FFC
32764
0x00
0x6000
24576
0x00
0x4000
16384
0x00
0x2000
8192
0x00
0x0000
0
0x00
0xE000
-8192
0x00
0xC000
-16384
0x00
0xA000
-24576
0x00
0x8000
-32768
0x00
0x8001
-32767
0x41
WAGO-I/O-SYSTEM 750
LED
Error
AI 1, 2
on
off
off
off
off
off
off
off
off
off
on
I/O Modules