2.1.2 750-479/000-001 [2 AI DC ±10 V Differential Measurement
Input/Sync]
2-Channel Analog Input Module DC ±10 V,
differential measurement input
(triggered only with coupler 750-303)
2.1.2.1

View

Function AI 1
Fig. 2.1.2-1: View
2.1.2.2

Description

This analog input module receives signals with standardized values of ±10 V.
The module works synchronously with the internal data bus for all
couplers/controllers used. When the module is connected to the Profibus
Fieldbus Coupler 750-303, the (fieldbus) network wide acquisition of
measured values can also be done synchronously. Triggering is done via this
special Profibus-DP/FMS (12 Mbaud) coupler. After receiving the command
"Global Control Command", the acquisition of measured values is initiated by
the coupler. A delay of one cycle is to be expected when scaling the measured
values. Sampling cycles ≥ 1 ms can be achieved.
The module has two differential input channels and can receive differential
signals via the connections +AI 1 and -AI 1 or +AI 2 and -AI 2.
The Shield (sreen) is directly connected to the DIN rail. A capacitive
connection is made automatically when snapped onto the DIN rail.
The input signal of each channel is electrically isolated and will be transmitted
with a resolution of 14 bits(13 bits + sign bit).
WAGO-I/O-SYSTEM 750
I/O Modules
750-479/000-001 [2 AI DC ±10 V Differential Measurement Input/Sync]
13 14
A
C
B
Error AI 1
D
+E1 +E2
+AI 1
-E1 -E2
-AI 1
S
S
Shield
(screen)
750-479
Function AI 2
Error AI 2
Data contacts
+AI 2
-AI 2
Shield
(screen)
• 13
View
g047900e