Overview Of Parameters - Siemens SIRIUS 3RW51 Equipment Manual

Soft starters and solid-state switching devices
Table of Contents

Advertisement

Display parameter values in the 3RW5 HMI (accessories)
• 3RW5 HMI Standard
While you are setting the parameters on the setting elements, the current value is shown and
cyclically updated on the display of the 3RW5 HMI Standard.
• 3RW5 HMI High Feature
While you are setting the parameters on the setting elements, the current value is shown and
cyclically updated on the display of the 3RW5 HMI High Feature in the "Parameters > Soft
Starter > Parameter list" menu.
6.2

Overview of parameters

Parameters
Trip class for motor overload
protection
Rated operational current I
the motor
1)
Current limiting value as a mul‐
tiple of the set rated operation‐
al current I
of the motor
e
Ramp-up time
Starting voltage
Stopping time
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
Symbol
of
e
Parameter assignment
6.2 Overview of parameters
Setting range
10A, 10E, 20E, OFF
1 ... 16
2)
1.3 ... 7 x I
e
max
The "max" setting
corresponds to 7
times the maximum
rated operating cur‐
rent Ie of the 3RW51
soft starter.
0 ... 20 s
With the setting "0 s",
the motor is switch‐
ed on with a ramp up
time of approx. 100
ms.
30 ... 100 %
0 ... 20 s
Factory setting
10A
16
4 x I
e
10 s
30 %
0 s
73