Functions
8.12 3RW5 HMI High Feature
Procedure for measured values
Select a measuring value.
The menus "Phase Currents [%]" and "Phase Currents (rms)" contain further menu items, which
you can switch to with "OK".
Measured value
Phase currents [%]
Phase currents (r.m.s.) [A]
Remaining motor cooling time
Remaining switching element cooling time
Switching element heating
3RW5 HMI High Feature firmware version V3.0 or higher
1)
110
Setting range
Explanation
IL1
The phase currents are displayed as a per‐
centage. You can monitor each phase (L1 /
IL2
L2 / L3) individually, or the average of all 3
IL3
phases.
Average
These measured values can be presented
graphically as a bar or line chart on the dis‐
play of the 3RW5 HMI High Feature.
You will find further information in chap‐
ters Design and operator controls of
the 3RW5 HMI High Feature (Page 116)
and Graphic display of measured values on
the 3RW5 HMI High Feature (Page 116).
The phase currents are displayed in am‐
peres. You can monitor each phase (L1 / L2 /
L3) individually, or the average of all 3 pha‐
ses.
These measured values can be presented
graphically as a bar or line chart on the dis‐
play of the 3RW5 HMI High Feature.
You will find further information in chap‐
ters Design and operator controls of
the 3RW5 HMI High Feature (Page 116)
and Graphic display of measured values on
the 3RW5 HMI High Feature (Page 116).
Remaining recovery time in seconds still to
be observed following activation of motor
protection until the 3RW51 soft starter is
once again ready for operation.
The remaining cooling-down period of the
switching element depends on the thermal
capacity of the power unit and the ambient
conditions (temperature, air circulation, in‐
stallation location, etc.). The remaining
cooling-down period of the switching ele‐
ment is stated in seconds.
The currently calculated switching ele‐
ment heating is continuously compared
with the previously saved switching ele‐
ment heating and indicated in %.
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
1)
1)
SIRIUS 3RW51 Soft Starter