Installing The 3Rw5 Hmi Standard On A Flat Surface - Siemens SIRIUS 3RW51 Equipment Manual

Soft starters and solid-state switching devices
Table of Contents

Advertisement

• Observe the coding of the plug and socket
• Lock the connector in the socket
• The HMI connecting cable in the cable duct of the 3RW5 HMI High Feature may only be routed
downward.
Make sure that you install the cable in accordance with EMC requirements. For example,
install data cables separately from the motor cable. Connect both sides of shielded cables
over a large surface area.
Result
You have installed the 3RW5 HMI High Feature in the cabinet door and can commission it
(Page 86).
4.5.7

Installing the 3RW5 HMI Standard on a flat surface

Requirements
• Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet
• 3RW5 HMI Standard (accessory)
• Level surface, e.g. sufficiently strong mounting plate
• 2 properly executed drill holes with thread or plugs on the level surface. Refer to the drilling
pattern (Page 163).
• 2 head screws M4 x 12 DIN ISO 7045 to fit the drill-holes
• Screwdriver (depending on the drive of the screws)
• 2 push-in lugs (accessory) for wall mounting (3ZY1311-0AA00)
• HMI connecting cable (accessory) of suitable length connected to the 3RW51 soft starter
Procedure
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
4.5 Installing / mounting / removing 3RW5 HMI
.
.
Mounting and Dismantling
49