Parameter assignment

6.2 Overview of parameters

6.2
Overview of parameters
Parameter
Trip class for motor overload
protection
Rated operational current I
motor
1)
Current limiting value as a multiple
of the set rated operational current I
of the motor.
Ramp up time
Starting voltage
Stopping time
Soft torque
RESET MODE
The rated operational current I
1)
specification of the manufacturer.
For meaning of scale, refer to the laser-inscribed table on front panel of device or in the Technical Data.
2)
100
Symbol
of the
e
e
of the motor may, according to the standard, deviate by 20% from the rating plate
e
Setting range
10A, 10E, 20E, OFF
1 ... 16
2)
1.3 ... 7 x I
e
max
The "max" setting corresponds to 7
times the maximum rated operating
current I
of the 3RW52 soft starter.
e
0 ... 20 s
With the setting "0 s", the motor is
switched on with a ramp up time of
approx. 100 ms.
30 ... 100%
0 ... 20 s
Off (LED off)
On (LED on)
Manual RESET (LED off)
Remote RESET (LED flashes green)
Auto RESET (LED lit green)
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Factory setting
10A
16
4 x I
e
10 s
30%
0 s
Off
Manual RESET
SIRIUS 3RW52 Soft Starter