Operating principle
If the 3RW5 soft starter, the 3RW5 HMI High Feature (accessory) or the 3RW5 communication
module (accessory) has to be replaced because of a fault, you can transfer data to your new
device (identical type) using the "Device change" function or SIRIUS Soft Starter ES (TIA Portal).
To be able to transfer data, you must first save it.
The following data are transferred with the "Device change" function:
• I&M 1 data
• I&M 3 data
• Device parameters of the 3RW5 HMI High Feature
• Communication parameters
Transmission options
• Device change with micro SD card on the 3RW5 HMI High Feature (Page 159)
10.5.1

Device change with micro SD card on the 3RW5 HMI High Feature

Requirements
• 3RW5 HMI High Feature (accessory)
• Micro SD card with the saved data (Page 125)
– The folder (e.g. "1P3RW5 xxx-xxxxx+SLO...") is located in the root directory (top level).
– The article number in the name of the folder must match the article number of the 3RW5
– Menu: "Micro SD card > Load communication and HMI parameters to micro SD card"
Procedure
1. Plug the micro SD card into the 3RW5 HMI High Feature.
2. Transfer the data to the device (3RW5 soft starter, 3RW5 HMI High Feature, 3RW5
communication module).
Menu: "Micro SD card > Device change"
Note
Device change
The current data of all devices (3RW5 soft starter, 3RW5 HMI High Feature, 3RW5
communication module) are overwritten by the data on the micro SD card.
3. Check the transferred data.
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
soft starter. The serial number in the name of the folder ("SLO...") does not need to match.
The data is saved in an automatically generated folder (e.g. "1P3RW5 xxx-xxxxx+SLO...").