Siemens SIRIUS 3RW51 Equipment Manual page 48

Soft starters and solid-state switching devices
Table of Contents

Advertisement

Mounting and Dismantling
4.5 Installing / mounting / removing 3RW5 HMI
• Continue to screw the screws into the fixing brackets
the front. Fasten the fixing brackets onto the 3RW5 HMI High Feature
• Tighten the 3RW5 HMI High Feature with a tightening torque of 0.3 ... 0.35 Nm
Ensure that all of the screw heads are in contact with the fixing bracket.
Procedure for installing the HMI connecting cable
• Use the opening to the cable duct
• It is possible to route the cable up or down in the cable duct.
Make sure that you install the cable in accordance with EMC requirements. For example,
route data cables separately from the motor cable. Connect both sides of shielded cables over
a large surface area.
Procedure for connecting with the HMI connecting cable
48
until they protrude approx. 8 mm at
to install the cable in the 3RW51 soft starter.
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
.
.
SIRIUS 3RW51 Soft Starter

Advertisement

Table of Contents
loading

Table of Contents