Output Voltage And Stand-By Specification Charts - Altronix ACM Series Installation Manual

Access power controllers with power supplies
Table of Contents

Advertisement

Altronix ACM Series units distribute and switch power to access control systems and accessories. They convert
a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These
power outputs can be converted to dry form "C" contacts. Outputs are activated by an open collector sink or
normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button,
PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The
fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACM Series Configuration Reference Chart:
Altronix
Model Number
AL400ULACM 3.5A
AL600ULACM 3.5A
AL1012ULACM 2.6A
AL1024ULACM 4.2A
Altronix
Model Number
AL400ULACM
AL600ULACM
AL1012ULACM
AL1024ULACM

Output Voltage and Stand-by Specification Charts:

AL400ULACM
Voltage
Switch Position
12VDC
SW1 - ON
24VDC
SW1 - OFF
AL600ULACM
Voltage
Switch Position
12VDC
SW1 - ON
24VDC
SW1 - OFF
AL1012ULACM
Voltage
Switch Position
12VDC
N/A
AL1024ULACM (refer to AL1024ULACM Battery Size Calculation Worksheet, pg. 10).
Stand-by
Voltage
Battery
24VDC
12AH
24VDC
65AH
- 2 -
5A/
15A/
0.7A 4A
250V
32V
5A/
0.7A 6A
250V
5A/
15A/
0.7A 10A
250V
32V
5A/
15A/
3.6A
250V
32V
* ANSI/UL 294 7th Ed. Access Control Performance Levels
Destructive
Attack
I
I
I
I
Stand-by Battery
40AH
40AH
Stand-by Battery
40AH
40AH
Stand-by Battery
40AH
15 mins. Stand-by /
5 mins. Alarm
7.7A / 9.7A
Overview:
3A
8
3.5A
P
6A
8
3.5A
8
3.5A
10A
8
3.5A
Endurance
Line
Test
Security
IV
IV
IV
IV
4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
3.5A / 3.5A
2.75A / 2.75A
4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
5.5A / 5.5A
5.75A / 5.75A
4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
9.5A / 9.5A
4 hr. Stand-by /
5 mins. Alarm
1.2A / 9.7A
7.7A / 9.7A
Agency Listings
Altronix Corp.
140 58th St. Brooklyn, NY
NYC
California
Dept. of
State Fire
Buildings
Marshal
LISTED
I
I
I
I
12AH - II, 40AH - III, 65AH - IV
0.75A / 2.75A
0.75A / 5.75A
24 hr. Stand-by /
5 mins. Alarm
1.2A / 9.7A
UL Listings
and
File Numbers
UL File # BP6714
UL 294*
UL Listed for
Access Control
System Units.
"Signal Equipment"
Evaluated to CSA
Standard C22.2
No.205-M1983
Stand-by
Power
I
I
I
0.5A / 3.5A
0.5A / 5.5A
0.5A / 9.5A
60 hr. Stand-by /
5 mins. Alarm
200mA / 9.7A
ACM Series