Altronix Maximal Series Installation Manual

Access power controllers
Hide thumbs Also See for Maximal Series:

Advertisement

Quick Links

Access Power Controllers
Installation Guide
Models Include:
Maximal11
- Power Supply 1:
12VDC @ 3.5A or 24VDC @ 2.7A.
- Power Supply 2:
12VDC @ 3.5A or 24VDC @ 2.7A.
- Sixteen (16) fuse protected
power-limited outputs.
Maximal33
- Power Supply 1:
12VDC @ 5.5A or 24VDC @ 5.7A.
- Power Supply 2:
12VDC @ 5.5A or 24VDC @ 5.7A.
- Sixteen (16) fuse protected
non power-limited outputs.
102512
Rev. DF
Altronix Corp.
140 58th St. Brooklyn, NY
Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
Series
Maximal55
- Power Supply 1: 12VDC @ 9.5A.
- Power Supply 2: 12VDC @ 9.5A.
- Sixteen (16) fuse protected
non power-limited outputs.
Maximal77
- Power Supply 1: 24VDC @ 9.7A.
- Power Supply 2: 24VDC @ 9.7A.
- Sixteen (16) fuse protected
non power-limited outputs.
Maximal75
- Power Supply 1: 12VDC @ 9.5A.
- Power Supply 2: 24VDC @ 9.7A.
- Sixteen (16) fuse protected
non power-limited outputs.
More than just power.
TM

Advertisement

Table of Contents
loading

Summary of Contents for Altronix Maximal Series

  • Page 1 - Sixteen (16) fuse protected - Power Supply 2: 24VDC @ 9.7A. non power-limited outputs. - Sixteen (16) fuse protected non power-limited outputs. Altronix Corp. 140 58th St. Brooklyn, NY More than just power. 102512 Rev. DF Available from A1 Security Cameras...
  • Page 2: Table Of Contents

    Table of Contents: Maximal Series Overview ....................3 Maximal Series Configuration Chart................3 Maximal Series Features ....................3-4 Maximal Installation Instructions.................. 4-5 Maintenance........................6 Power Supply Board LED Diagnostics ................6 Access Power Controller LED Diagnostics ..............6 Power Supply Board Terminal Identification ..............7 Access Power Controller Terminal Identification............
  • Page 3: Maximal Series Overview

    The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed. Maximal Series Configuration Chart: Altronix Output Voltage Options...
  • Page 4: Maximal Installation Instructions

    • Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs. Fire Alarm disconnect input trigger options: a) Normally open (NO) or normally closed (NC) dry trigger input. b) Polarity reversal input from FACP signaling circuit. •...
  • Page 5 5. Output options (Fig. 2, pg. 9): The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any combination of both switched power and form “C” outputs. (a) Fail-Safe Switched Power outputs: For Fail-Safe operation connect the positive (+) input of the access control devices to the terminal marked [NC]. Connect the negative (-) input of the access control devices to the terminal marked [COM].
  • Page 6: Maintenance

    Maintenance: Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect.
  • Page 7: Power Supply Board Terminal Identification

    Power Supply Board Terminal Identification: Terminal Function/Description Legend L, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. Maximal11 - 12VDC @ 3.5A or 24VDC @ 2.7A to ACM8 boards (power-limited). Maximal33 - 12VDC @ 5.5A or 24VDC @ 5.7A to ACM8 boards (non power-limited). Maximal55 - 12VDC @ 9.5A to ACM8 boards (power-limited).
  • Page 8: Power Supply Board Stand-By Battery Specifications

    Power Supply Board Stand-by Battery Specifications: Altronix Power Supply Board Battery 20 Min. of Backup 4 Hr. of Backup 24 Hr. of Backup Model AL400ULXB2 12VDC/40AH* 3.5A 0.5A (Refer to Fig. 1a, pg. 9 Maximal11 for Switch [SW1] 24VDC/40AH* 2.7A 0.7A...
  • Page 9: Power Supply Board Output Voltage Settings

    Power Supply Board Output Voltage Settings: Fig. 1 Fig. 1a OFF - 24V ON - 12V OFF - 24V ON - 12V Maximal11/Maximal33 - Power Supply Board Access Power Controller Typical Application Diagram (for each ACM8): Fig.2 Fig. 2a Intact = Dry Input Normally Open (N.O.) Cut = Wet Input Door Releasing...
  • Page 10: Maximal11, Maximal33 And Maximal55 Battery Hookup And Tamper Switch Installation

    Fig. 3 Maximal11 Maximal33 Maximal55 Tamper Switch Power Supply Board BAT FAIL AC FAIL NC C NO NC C NO Line Neutral Wire Strap Power Supply Board (from Enclosure to Door) BAT FAIL AC FAIL NC C NO NC C NO 115VAC Input Line Neutral...
  • Page 11: Maximal77 Battery Hookup And Tamper Switch Installation

    Fig. 4 Maximal77 Tamper Switch Power Supply Board BAT FAIL AC FAIL NC C NO NC C NO Line Neutral Wire Power Supply Board Strap (from Enclosure to Door) BAT FAIL AC FAIL NC C NO NC C NO 115VAC Input Line Neutral 60 Hz.
  • Page 12: Maximal75 Battery Hookup And Tamper Switch Installation

    Fig. 5 Maximal75 Tamper Switch Power Supply Board BAT FAIL AC FAIL NC C NO NC C NO Line Neutral Wire Strap Power Supply Board (from Enclosure to Door) BAT FAIL AC FAIL NC C NO NC C NO 115VAC Input Line Neutral 60 Hz.
  • Page 13: Nec Power-Limited Wiring Requirements For Maximal11

    NEC Power-Limited Wiring Requirements for Maximal11: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 14: Nec Power-Limited Wiring Requirements For Maximal33 And Maximal55

    NEC Power-Limited Wiring Requirements for Maximal33 and Maximal55: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
  • Page 15: Nec Power-Limited Wiring Requirements For Maximal77

    NEC Power-Limited Wiring Requirements for Maximal77: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 16: Nec Power-Limited Wiring Requirements For Maximal75

    NEC Power-Limited Wiring Requirements for Maximal75: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 17: Facp/Optional Power Supply Hook-Up Diagrams

    FACP/Optional Power Supply Hook-up Diagrams: Fig. 10 Optional hook-up using two (2) isolated power Fig. 11 Polarity reversal input from FACP signaling circuit supply inputs (Only applicable on Maximal11): output (polarity is referenced in alarm condition): CUT JUMPERS JUMPER J1 AND J2 FACP OUTPUT EOL ISOLATED POWER INPUT...
  • Page 18: Enclosure Dimensions

    Enclosure Dimensions (H x W x D approximate) 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm) 19” (482.6mm) 2” 4” 7” 4” 2” (50.8mm) (101.6mm) (177.8mm) (101.6mm) (50.8mm) 6.25” (158.75mm) 19” 1.25” (482.6mm) (31.75mm) 1.25” 0.85” 0.85” 8.9” 8.4”...
  • Page 19 Notes: Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused) - 19 ­ Available from A1 Security Cameras www.a1securitycameras.com email: sales@a1securitycameras.com...
  • Page 20 Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 web site: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. MEMBER IIMaximal11/33/55/75/77 Series I13Q...