Tests
3.2 Function test
3.2.5

Socket outlets and lighting

Fundamentals
Socket outlets and lighting are checked.
Test procedure
1. The voltage at the socket outlets is measured.
2. The lighting is checked.
Result
The test is passed if the correct voltage is available at the socket outlets and the lighting
functions.
3.2.6

Remote access via digital and analog inputs and outputs

Fundamentals
With the drive in the remote mode, a check is made as to whether it can be controlled via digital
and analog inputs and outputs.
Test procedure
1. The drive is switched into the remote mode using the "Local-Remote switch".
2. The following operating states are set and monitored at the test station:
Result
The test is passed if the corresponding operating states and specified values occur.
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
22
– Ready to switch on
– Remote mode
– Drive on
– Drive off
– Various points along the U/f characteristic
– Reset fault
– Remote inhibit
– Emergency Off
N30 N35 N44 N75 M08 U10 Y15