UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Figure 4-10 IP settings
IP address allocation
Item
IP address
Subnet mask
Gateway
Figure 4-11 RS485 communication settings
Item
Comm Address
Issue 03 (2019-12-13)
Manual: After the MDU connects to the PC over a network cable, check that their IP
addresses are two different values on the same network segment.
Automatic: The MDU automatically queries available IP addresses in the connected
network. Ensure that the MDU and PC are on the same network segment.
You can set Allocation to Manual or Automatic. If the UPS is restarted, Allocation automatically
changes to Manual. The IP address is bound as the IP address set last time, allowing you to log in for
the second time.
Description
Specifies the IP address for the
Ethernet.
NOTICE
Ensure that the UPS IP address is
unique on the network segment.
Otherwise, the WebUI display
function may not function properly.
Specifies the subnet mask of the
Ethernet.
Specifies the Ethernet gateway.
Description
This serial port address is
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
192.168.0.10
1.0.0.0–223.255.
255.255
255.255.255.0
0.0.0.0–255.255.
255.255
192.168.0.1
1.0.0.0–223.255.
255.255
Default Value
Value Range
1
1–254
89