Huawei UPS5000-E-25K-SM User Manual page 166

Table of Contents

Advertisement

UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
Electromagnetic
compatibility (EMC)
Table 8-4 Mains input electrical specifications
Item
System
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Harmonic current
Issue 03 (2019-12-13)
Specifications
CQC
TLC
Conducted emission
Radiated emission (RE)
Low-frequency signal
interference
Electrostatic discharge
immunity
Conducted susceptibility
Radiated susceptibility
Electrical fast transient (EFT)
Surge protection
Lightning protection
Power frequency magnetic
field
Voltage dip and temporary
interruption (220 V AC)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
At 0–40° C: not derated when the voltage is 176–280 V AC;
derated to 40% load when the voltage is 176–80 V AC.
50/60 Hz
40–70 Hz
> 0.99 (full load)
> 0.98 (half load)
THDi ≤ 3% (full linear load)
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
GB7260.1-2008
YD/T2165-2010
EN/IEC62040-2
EN/IEC62040-2
IEC61000-2-2
IEC61000-4-2
EN/IEC62040-2
EN/IEC61000-4-6
EN/IEC62040-2
EN/IEC61000-4-3
EN/IEC62040-2
IEC61000-4-4
EN/IEC62040-2
IEC61000-4-5
YD/T 1095-2008
IEC 61000-4-8
IEC61000-4-11
158