UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
connector
Output
connector
Battery
input
connector
Issue 03 (2019-12-13)
Recommended
cross-sectional
2
area (mm
)
Output current (A)
Recommended
cross-sectional
2
area (mm
)
Nominal discharge
current (A)
Maximum discharge
current (A)
Recommended
cross-sectional
2
area (mm
)
When installation environment (such as routing mode and ambient temperature) changes,
prepare cables based on specifications in IEC60364-5-52 or local standards.
When the mains input and bypass input share a power source, configure mains input
power cables as input power cables. The cables listed in
the following requirements are met:
The cables are installed along the wall or on the floor (IEC60364-5-52 C standards).
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%. The
recommended cross-sectional areas in
requirements. Users should evaluate the line voltage loss based on the actual cable
length. If the voltage loss exceeds the requirements, increase the cable
cross-sectional areas properly.
90° C copper-core cables are used.
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
Copyright © Huawei Technologies Co., Ltd.
25 kVA
L1
4 x 10
L2
L3
N
PE
10
38
U
4 x 6
V
W
N
PE
6
69
83
+
35
N
-
PE
16
Table 3-2
50 kVA
75 kVA
4 x 25
4 x 50
25
25
76
114
4 x 16
4 x 25
16
25
138
206
165
247
50
95
25
50
Table 3-2
are used only when
meet the basic through-current
3 Installation
42