UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Step 3 Check that the EPO alarm has disappeared from the alarm list. If the bypass is normal, the
UPS transfers to bypass mode.
Step 4 Start the inverter.
----End
Issue 03 (2019-12-13)
Figure 5-21 Alarms screen
Figure 5-22 Clearing the alarm
WebUI
On the WebUI, choose Monitoring > Control and click Clear Fault to clear the EPO
alarm, as shown in
Figure
Figure 5-23 Clearing the alarm on the WebUI
Copyright © Huawei Technologies Co., Ltd.
5-23.
5 Operations
147