UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
hibernate
Module cycle
hiber. period
(d)
D.G. ECO
bypass supply
RAM
verification
Collect
real-time site
waveform
BCB trips in
case of EOD
Input Setting
Item
D.G. mode
Issue 03 (2019-12-13)
Description
enable parallel hibernation to
alternate modules in hibernation
mode, which can prolong their
service life and improve the
system efficiency.
Indicates the rotation interval of
modules in hibernation mode.
The default value is 30, which
means that the hibernating
module is rotated every 30 days.
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
Enable or disable the memory
check function. If this parameter
is set to Enable, the control chip
RAM working status is checked
regularly. If this parameter is set
to Disable, regular check is
disabled.
If this parameter is set to Enable,
one waveform can be stored
manually.
If this parameter is set to Enable,
the BCB will trip in case of
EOD.
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
30
1–100
Enable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
Enable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
107