UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
Cell float volt.
Flt. volt. comp.
Temp. comp.
coef.
Temp. comp.
center
Item
Max. dis. time
Issue 03 (2019-12-13)
Description
Indicates the battery float
charging voltage. The parameter
is configurable in any mode.
Option to correct the float
voltage based on the battery
temperature when a battery
temperature sensor is connected.
The value is configurable in any
mode.
Coefficient for correcting the
float voltage based on the battery
temperature when a battery
temperature sensor is connected.
Basic point of temperature
compensation.
Discharge
Figure 4-23 Discharge screen
Description
Indicates the maximum battery
discharge time. When the
discharge time reaches the value,
the UPS powers off.
Shallow Discharge Test
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
2.25 V/cell
2.23 V/cell–2.30
V/cell
Enabled
Disable, Enable
3.3 mV/° C*cell
0.0
mV/° C*cell–6.0
mV/° C*cell
25 ° C
20–30
Default Value
Value Range
24h
16h–48h
98