UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
Minimum cell voltage
Table 8-7 Output electrical specifications
Item
System
Voltage
Frequency
THDv
Power factor
Transfer time
Output voltage imbalance
Overload capability
Table 8-8 System electrical specifications
Item
Parallel reliability
Parallel ECO function
Issue 03 (2019-12-13)
Specifications
2.23–2.30 V/cell. The default voltage is 2.25 V/cell (30–44
batteries).
1.6–1.9 V/cell
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
In normal mode, the frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50/60 Hz with a tolerance
of ± 0.05%.
THDv ≤ 1% (full linear load)
THDv ≤ 4% (full non-linear load)
1
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Voltage imbalance: ± 3%; phase imbalance: ± 2°
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60
minutes
110% < load ≤ 125%: transfer to bypass mode after 10
minutes
125% < load ≤ 150%: transfer to bypass mode after 1
minute
Load > 150% or a short circuit occurs: run for 200 ms
Specifications
Redundant parallel signals
Supported
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications