Huawei UPS5000-E-25K-SM User Manual page 105

Table of Contents

Advertisement

UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
strin
Num of batt.
strin
Maint. period
Cur. limit coef
Item
Cell eql. volt.
Auto. eql. chg.
Issue 03 (2019-12-13)
Description
in a battery string.
Specifies the number of battery
strings connected in parallel.
Specifies the interval for
reminding users of battery
maintenance.
The charging current limit is a
multiple of the battery capacity.
Equalized Charge
Figure 4-21 Equalized Charge screen
Description
Indicates the battery equalized
charging voltage. The parameter
is configurable in any mode.
When the value is Enabled, the
UPS automatically changes the
battery management status to
equalized charge based on the
charge current and floating
charge time.
Float Charge
Figure 4-22 Float Charge screen
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
on the model.
model.
1
1–4
0
0–365
0.1C10
0.05C10 to
0.15C10
Default Value
Value Range
2.30
2.35 V/cell
V/cell–2.40
V/cell
Enabled
N/A
97