Huawei UPS5000-E-25K-SM User Manual page 107

Table of Contents

Advertisement

UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
Item
Scheduled test
Time
Time interval
Discharge ratio
Issue 03 (2019-12-13)
Figure 4-24 Shallow Discharge Test screen
Description
When certain conditions are met,
the charger shuts down, the UPS
transfers from normal mode to
battery mode, and batteries
supply power to loads. The UPS
records the battery discharge data
as a reference for battery reserve
and lifespan.
The shallow discharge test starts
in the specified time.
Indicates the time interval for
shallow discharge tests The
parameter is configurable in any
mode.
Indicates the proportion of the
discharge capacity to the total
discharge capacity. The
parameter is configurable in any
mode.
Backup time
Figure 4-25 Backup time screen
Warning thresh. parameter
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
Disable
Disable, Enable
00:00–06:00
00:00–06:00,
06:00–12:00,
12:00–18:00, or
18:00–24:00.
60d
30d–90d
20%
10%–50%
99