Bender ISOMETER isoCHA425 Manual page 21

Insulation monitoring device for unearthed dc systems (it systems), dc 50 v up to 400 v, suitable for the charging of electric vehicles acc. to japanese charging standard chademo, software version: d612 v1.xx
Hide thumbs Also See for ISOMETER isoCHA425:

Advertisement

Data access using the Modbus RTU protocol
7.3 Exception code
If a request cannot be answered for whatever reason, the ISOMETER® will send a so-called
exception code with which possible faults can be narrowed down.
Exception code
0x01
Impermissible function
0x02
Impermissible data access
0x03
Impermissible data value
0x04
Internal fault
0x05
Acknowledgement of receipt (answer will be time delayed)
0x06
Request not accepted (repeat request, if necessary)
7.3.1 Structure of the exception code
Byte
Name
Byte 0
ISOMETER® Modbus address
Byte 1
Function code (0x03) + 0x80
Byte 2
Data (exception code)
Byte 3, 4
CRC16 Checksum
21
Description
Example
0x03
0x83
0x04
0xE133
Data access using the Modbus RTU protocol
isoCHA425_D00352_01_M_XXEN/10.2019