41
—
5.4 Environmental conditions
Environmental
Operating temperature range
Storage temperature range
Relative humidity
Max. altitude without derating
Pollution degree
Protection class
Cooling
Air flow
Heat dissipation
Acoustic noise at 1 m
—
Table 5.05: HiPerGuard
MV UPS environmen-
tal specifications
—
5.5 Interface
Interface
System display
Display advanced functionality
Communication
Hardwired interface
—
Table 5.06: HiPerGuard
MV UPS interface
specifications
0 °C - 40 °C
-20 °C - +60 °C
5 – 85 %
1000 m
2
IP21
Forced air
20,000 m³/hour
< 45 kW
< 80 dBA
10" touchscreen display
Waveform capturing
Event analysis
Trending
Comprehensive service log
Ethernet
Modbus TCP
Digital inputs
Relay outputs
1
Excluding energy storage.
Daily and yearly max. Aver-
ages apply, nominal system
temperature is based on 25°C
Excluding energy storage
No condensation
Under nominal conditions