Name
Address
003Eh
003Fh
0040h
0041h
【ECI Group】
Name
Address
0046h
0047h
0048h
0049h
Range
0~9
Relay 3 Energized Mode
0: oFF(no use);
1: btCH.n(Batch with N Mode)
2: btCH.r(Batch with R Mode)
3: btCH.C(Batch with C Mode)
4: btCH.E(Batch with E Mode)
5: totL.n(Totalizer with N Mode)
6: totL.r(Totalizer with R Mode)
7: totL.C(Totalizer with C Mode)
8: totL.E(Totalizer with E Mode)
9: Do(Digital Output)
0000~5999
Relay 3 Energized Time
(0.1second)
0~9
Relay 4 Energized Mode
0: oFF(no use);
1: btCH.n(Batch with N Mode)
2: btCH.r(Batch with R Mode)
3: btCH.C(Batch with C Mode)
4: btCH.E(Batch with E Mode)
5: totL.n(Totalizer with N Mode)
6: totL.r(Totalizer with R Mode)
7: totL.C(Totalizer with C Mode)
8: totL.E(Totalizer with E Mode)
9: Do(Digital Output)
Relay 4 Energized Time
0000~5999
(0.1second)
Range
External Control Input 1
0~6
0:nonE (None);
1: GAtE(Gate for Totalizer & Batch)
2: rESEt(Reset for Totalizer & Batch)
3: tL.GtE(Gate for Totalizer)
4: tL.rSt(Reset for Totalizer)
5: bt.GtE(Gate for Batch)
6: bt.rSt(Reset for Batch)
External Control Input 2
0~6
0:nonE (None);
1: GAtE(Gate for Totalizer & Batch)
2: rESEt(Reset for Totalizer & Batch)
3: tL.GtE(Gate for Totalizer)
4: tL.rSt(Reset for Totalizer)
5: bt.GtE(Gate for Batch)
6: bt.rSt(Reset for Batch)
External Control Input 3
0~6
0:nonE (None);
1: GAtE(Gate for Totalizer & Batch)
2: rESEt(Reset for Totalizer & Batch)
3: tL.GtE(Gate for Totalizer)
4: tL.rSt(Reset for Totalizer)
5: bt.GtE(Gate for Batch)
6: bt.rSt(Reset for Batch)
ECI debouncing
5~255
5~250 16mSec
Explain
Explain
18 / 19
Initial
Write/Read Note
1
R/W
10
R/W
3
R/W
10
R/W
Initial
Write/Read Note
1
R/W
2
R/W
4
R/W
12
R/W
CS2-MC Manual 2014/9/9