Structure As Of Byte X+8 For Diagnostic Interrupt (Analog Inputs) - Siemens SIMATIC ET 200M Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

Diagnostic Interrupt of Modules with Analog Inputs
Byte x+4
See Figure 6-11 on page 6-32
:
Byte x+7
Byte x+8
Byte x+9
Byte x+10
7
6
5
4
3
Byte x+11
:
:
Diagnostic event on channel/channel group 7 of the module
6
5
4
3
2
7
Byte x+12
Short circuit to L+
Short-circuit to M
Wire break
Reference channel error
Lower limit violation
Upper limit violation
Byte x+13: Assignment for channel/channel group 1 as for byte x+12
:
Byte x+19: Assignment for channel/channel group 7 as for byte x+12
Figure 6-14

Structure as of byte x+8 for diagnostic interrupt (analog inputs)

Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
71
: Module with analog inputs
H
61
: Module with HART analog inputs
H
Length of the channel-specific diagnosis
Number of channels per module
2
1
0
Diagnostic event on the channel/channel group 0 of the module
Diagnostic event on the channel/channel group 1 of the module
1
0
Configuration/parameter assignment error
Common-mode error
Commissioning and Diagnostics
6-35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents