Commissioning and Diagnostics
Switch on the supply voltage
for the IM 153-2 (a)
IM 153-2Bx00 only:
All LEDs light up for a few
seconds during internal tests
The "ON" and "BF" LEDs come on
IM 153-2
(a) checks
whether it is inserted
on the BM IM/IM
Yes
IM 153-2 (a)
checkswhether
the IM 153-2 (b)
is inserted
Yes
Has the
IM 153-2 (b) already
received configuration data
from the DP master, has it tested
them with the ET 200M configuration,
and is it exchanging data
with the DP master?
Yes
... then the IM 153-2(a)
is passive
The IM 153-2 (a) receives all
the ET 200M data from the
IM 153-2 (b) (if available)
- Actual configuration
- PROFIBUS status
- Queued interrupts
- Time stamp messages
The IM 153-2 (a) receives
configuration data from
the associated DP master
Does the
configuration data
match that
of the IM 153-2 (b)?
Yes
The "BF" LED goes out. The IM 153-2
(a) is ready for data transfer, and is in
standby mode when switchover is
required
Figure 6-3
Startup of the IM 153-2
6-6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
No
No configuration
for "redundancy"
... then the
No
IM 153-2(a) is
active
IM 153-2 (a) receives
No
the configuration data
from the DP master
Does the
configuration
data match the
real configuration?
Yes
The "BF" LED goes out;
the "ACT" LED comes on.
data transfer is possible
The configuration data is
No
rejected; error message to
DP master
Match up the configuration
data in the DP master
Startup as in
Figure 6-1 on
Page 6-4
Time
synchronization
No
Data transfer only takes
place with modules that
correspond to the desired
configuration (other modules
or missing modules are
reported by the IM 153-2 in
the module diagnosis)
Time
synchro-
nization
Distributed I/O Device ET 200M
EWA-4NEB780600602-06