Commissioning and Diagnostics
Example of Displaying the S7 Diagnosis Using SFC 13 "DPNRM_DG"
Here you will find an example of how to use SFC 13 to display the slave diagnosis
for a DP slave in the STEP 7 user program.
Assumptions
The following assumptions apply to this STEP 7 user program:
S The diagnostic address of the ET 200M is 1022 (3FE
S The slave diagnosis should be stored in DB 82:
as of address 0.0, length 64 bytes.
S The slave diagnosis consists of 64 bytes.
STEP 7 User Program
STL
CALL
SFC 13
REQ
:=TRUE
LADDR
:=W#16#3FE
RET_VAL :=MW 0
RECORD :=P#DB82.DBX 0.0 BYTE 64
BUSY
:=M2.0
6-14
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Description
Read request
Diagnostic address of the ET 200M
RET_VAL of SFC 13
Data mailbox for the diagnosis in DB 82
Read operation runs over several OB1 cycles
).
H
Distributed I/O Device ET 200M
EWA-4NEB780600602-06