Structure Of The Channel-Specific Diagnosis - Siemens SIMATIC ET 200M Manual

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

as of
Byte 16
Code for channel-specific diagnosis
Byte 17
Byte 18
Bytes 19
to 21
Max. byte 63 in the IM 153-1
and byte 95 in the IM 153-2
Figure 6-8

Structure of the channel-specific diagnosis

Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
7
6 5 4
3 2
1
0
Bit no.
1 0
000001
to 001010
B
channel-specific diagnosis.
(Example: Slot 4 has ID no. 3;
Slot 5 has ID no. 4)
7
6 5 4
3 2
1
0
Bit no.
000000
to 111111
: Number of the channel or the channel group
B
B
that delivers the diagnosis
Input/output:
01
: Input
B
10
: Output
B
11
: Input/output
B
7
6 5 4
3 2
1
0
Bit no.
Error type
In accordance with the PROFIBUS standard
(see Tables 6-12 on page 6-26
Channel type
and 6-13 on page 6-27)
001
: Bit
B
010
: 2 Bit
B
011
: 4 Bit
B
100
: Byte
B
101
: Word
B
110
: 2 words
B
Next channel-specific diagnostic message
(assignment as for bytes 16 to 18)
Commissioning and Diagnostics
: ID number of the module that delivers the
B
6-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents