Commissioning and Diagnostics
Table 6-6
Status and error messages of the IM 153-2
IM 153-2AA02/-2AB01
SF
BF
ACT
ON
LEDs
SF
BF
ACT
ON
*
On
Off
On
No connection to the DP master
(baud rate detection)
Causes:
S
On
Off
On
The configured setup of the ET 200M
Flashes
does not match the actual setup of
the ET 200M.
On
Off
Off
On
Invalid PROFIBUS address
Is the SF LED of an SM/FM also on?
If so: There is an error or a diagnosis
in an S7-300 module
If not: The IM 153-2 is defective.
*
Off
On
On
The IM 153-2 is involved in data
exchange with the DP master and the
I/O modules of the ET 200M.
In the case of redundancy, this
IM 153-2 is the active one of the
ET 200M.
*
Off
Off
On
There is voltage applied to the IM
153-2. In the case of redundancy this
IM 153-2 is the passive one, i.e. it
does not exchange data with the I/O
modules.
Off
Off
On
In redundancy mode, this IM 153-2 is
Flashes
0.5Hz
passive and not ready for a
bumpless switchover (for example,
switching the associated CPU to
STOP).
*
Not applicable
** After transition to redundant mode, the SF LED flashes for a further 20 s.
6-12
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
IM 153-2Bx00
SF
SF (group fault):
BF
BF (fault at PROFIBUS):
ACT (active module in redundancy mode):
ON (supply voltage available):
ACT
ON
Meaning
The bus communication via
PROFIBUS-DP to the IM 153-2
has been interrupted.
red
red
yellow
green
What to Do
Check the bus setup.
S
Check that the bus
connector/fiber-optic cable is
correctly inserted.
S
Check if the interconnecting
cable/fiber-optic cable to the DP
master has been interrupted.
S
Switch the 24 V DC switch on the
power supply module off and then
on again.
Check the ET 200M configuration, to
find out if a module is missing or
defective or whether an unconfigured
module is inserted.
Check the configuration (for
example with COM PROFIBUS or
STEP 7).
Set a valid PROFIBUS address (1 to
125) on the IM 153-2.
Check the SM/FM with the diagnosis.
Change the S7-300 module or the IM
153-2 or contact your Siemens
partner.
Put the fault-tolerant system into the
redundant state.
Distributed I/O Device ET 200M
EWA-4NEB780600602-06