7.6

Replacing the Bus Module

Removing the Bus Module
Only remove bus modules if they are de-energized!
Table 7-7
Removing the bus module
Step
1.
Put the on/off switch of the power supply module into the 0 position
( : output voltage 0 V).
2.
Remove the modules on the bus module that is be replaced, on all the bus modules on the
right, as well as the module directly to the left.
3.
The bus modules are locked together. On the bus module that is to be replaced, press down
the lock of the bus module on the right, and push the bus module(s) on the right to the right.
4.
On the bus module on the left, press down the lock of the bus module that is to be replaced
and push this one to the right.
Using a screwdriver push the lock down towards the rail.
5.
6.
Lift the bus module off the rail. You can also pull the bus module out from the right side of the
rail.
BM IM/PS
Installing a New Bus Module
Install the new bus module as described in Section 4.2.3.
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Removing the Bus Module
Lock holding the bus
modules together
BM 2 40