Specifications
8.7.1 CE Compliance
200–240 V
Enclosure
A1
A2
A3
A4
A5
B1
B2
8
8
B3
B4
C1
C2
C3
C4
Table 8.13 200–240 V, Enclosure Types A, B and C
70
Power [kW]
Recommended
fuse size
0.25–1.5
gG-10
0.25–2.2
gG-10 (0.25–1.5)
gG-16 (2.2)
3.0–3.7
gG-16 (3)
gG-20 (3.7)
0.25–2.2
gG-10 (0.25–1.5)
gG-16 (2.2)
0.25–3.7
gG-10 (0.25–1.5)
gG-16 (2.2–3)
gG-20 (3.7)
5.5–7.5
gG-25 (5.5)
gG-32 (7.5)
11
gG-50
5.5
gG-25
7.5–15
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
15–22
gG-63 (15)
gG-80 (18.5)
gG-100 (22)
30–37
aR-160 (30)
aR-200 (37)
18.5–22
gG-80 (18.5)
aR-125 (22)
30–37
aR-160 (30)
aR-200 (37)
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Instruction Manual
Recommended
Max. fuse
gG-25
gG-25
gG-32
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160 (15–18.5)
aR-160 (22)
aR-200 (30)
aR-250 (37)
gG-150 (18.5)
aR-160 (22)
aR-200 (30)
aR-250 (37)
Recommended circuit
Max trip level [A]
breaker Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
16
25
25
25
25
63
100
50
100
160
250
150
250
MG33AN22