Danfoss VLT AutomationDrive FC 301 Instruction Manual page 44

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Diagnostics and Troubleshoo...
WARNING/ALARM 12, Torque limit
The torque has exceeded the value in 4-16 Torque Limit
Motor Mode or the value in 4-17 Torque Limit Generator
Mode. 14-25 Trip Delay at Torque Limit can change this
warning from a warning-only condition to a warning
followed by an alarm.
Troubleshooting
If the motor torque limit is exceeded during
ramp-up, extend the ramp-up time.
If the generator torque limit is exceeded during
ramp-down, extend the ramp-down time.
If torque limit occurs while running, possibly
increase the torque limit. Make sure that the
system can operate safely at a higher torque.
Check the application for excessive current draw
7
7
on the motor.
WARNING/ALARM 13, Over current
The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts about 1.5 s,
then the adjustable frequency drive trips and issues an
alarm. Shock loading or quick acceleration with high inertia
loads can cause this fault. It can also appear after kinetic
backup if the acceleration during ramp-up is quick. If
extended mechanical brake control is selected, trip can be
reset externally.
Troubleshooting
Remove power and check if the motor shaft can
be turned.
Make sure that the motor size matches the
adjustable frequency drive.
Check parameters 1-20 to 1-25 for correct motor
data.
ALARM 14, Earth (ground) fault
There is current from the output phases to ground, either
in the cable between the adjustable frequency drive and
the motor or in the motor itself.
Troubleshooting
Remove power to the adjustable frequency drive
and repair the ground fault.
Check for ground faults in the motor by
measuring the resistance to ground of the motor
leads and the motor with a megohmmeter.
42
Instruction Manual
ALARM 15, Hardware mismatch
A fitted option is not operational with the present control
board hardware or software.
Record the value of the following parameters and contact
your Danfoss supplier:
ALARM 16, Short circuit
There is short-circuiting in the motor or motor wiring.
Remove power to the adjustable frequency drive and
repair the short circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the adjustable frequency
drive.
The warning is only active when 8-04 Control Word Timeout
Function is NOT set to [0] Off.
If 8-04 Control Word Timeout Function is set to [5] Stop and
Trip, a warning appears and the adjustable frequency drive
ramps down until it stops then displays an alarm.
Troubleshooting
WARNING/ALARM 20, Temp. input error
The temperature sensor is not connected.
WARNING/ALARM 21, Parameter error
The parameter is out of range. The parameter number is
reported in the LCP. The affected parameter must be set to
a valid value.
WARNING/ALARM 22, Hoist mechanical brake
Report value shows what kind it is.
0 = The torque ref. was not reached before timeout
(Parameter 2-27).
1 = Expected brake feedback not received before timeout
(Parameters 2-23, 2-25).
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-45 Actual Typecode String
15-49 SW ID Control Card
15-50 SW ID Power Card
15-60 Option Mounted
15-61 Option SW Version (for each option slot)
Check connections on the serial communication
cable.
Increase 8-03 Control Word Timeout Time
Check the operation of the communication
equipment.
Verify a proper installation based on EMC
requirements.
MG33AN22

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents