Line Power Supply 3X525-600 V Ac (Fc 302 Only) - Danfoss VLT AutomationDrive FC 301 Instruction Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Specifications
8.1.3 Line Power Supply 3x525–600 V AC (FC 302 only)
Type Designation
Typical Shaft Output [hp] [kW]
Enclosure IP20, IP21
Enclosure IP55
Output current
Continuous (3 x 525–550 V) [A]
Intermittent (3 x 525–550 V) [A]
Continuous (3x551–600 V) [A]
Intermittent (3x551–600 V) [A]
Continuous kVA (525 V AC) [kVA]
Continuous kVA (575 V AC) [kVA]
Max. input current
Continuous (3x525–600 V) [A]
Intermittent (3x525–600 V) [A]
Additional specifications
Max. cable cross-section
4)
for line power, motor,
brake and load sharing [mm
2
] ([AWG])
4)
Max. cable cross-section
for disconnect
2
[mm
] ([AWG])
Estimated power loss at rated max. load hp
[W]
3)
2)
Efficiency
Table 8.7 Line Power Supply 3x525–600 V AC (FC 302 only), PK75-P7K5
MG33AN22
Instruction Manual
PK75
P1K1
P1K5
1 [0.75]
1.5 [1.1]
2.0 [1.5]
A3
A3
A3
A5
A5
A5
1.8
2.6
2.9
2.9
4.2
4.6
1.7
2.4
2.7
2.7
3.8
4.3
1.7
2.5
2.8
1.7
2.4
2.7
1.7
2.4
2.7
2.7
3.8
4.3
0.047 [35] 0.068 [50] 0.088 [65] 0.124 [92]
0.97
0.97
0.97
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
P2K2
P3K0
P4K0
3.0 [2.2]
4.0 [3.0]
5.0 [4.0]
A3
A3
A3
A5
A5
A5
4.1
5.2
6.4
6.6
8.3
10.2
3.9
4.9
6.1
6.2
7.8
9.8
3.9
5.0
6.1
3.9
4.9
6.1
4.1
5.2
5.8
6.6
8.3
9.3
4,4,4 (12,12,12)
(min. 0.2 (24))
6,4,4 (10,12,12)
0.165
0.196
[122]
[145]
0.97
0.97
0.97
P5K5
P7K5
7.5 [5.5]
10 [7.5]
A3
A3
A5
A5
9.5
11.5
15.2
18.4
9.0
11.0
14.4
17.6
9.0
11.0
9.0
11.0
8.6
10.4
13.8
16.6
8
0.264
0.353
[195]
[261]
0.97
0.97
57