Electrical Installation

4.8.1 Control Terminal Types

Figure 4.7 and Figure 4.8 show the removable adjustable
frequency drive connectors. Terminal functions and default
settings are summarized in Table 4.3 and Table 4.4.
Figure 4.7 Control Terminal Locations
1
12 13 18 19 27 29 32 33 20 37
2
3
61 68 69
39 42 50 53 54 55
Figure 4.8 Terminal Numbers
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO (Safe Torque Off)
function
Connector 2 terminals (+)68 and (-)69 for RS-485
serial communication connection
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
MG33AN22
Instruction Manual
Terminal
12, 13
4
1
Table 4.3 Terminal Description Digital Inputs/Outputs,
Analog Inputs/Outputs
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
Terminal description
Default
Parameter
setting
Digital inputs/outputs
-
+24 V DC
18
5-10
[8] Start
19
5-11
[10] Reversing
32
5-14
[0] No
operation
33
5-15
[0] No
operation
27
5-12
[2] Coast
inverse
29
5-13
[14] JOG
20
-
37
-
Safe Torque
Off (STO)
Analog inputs/outputs
39
-
42
6-50
[0] No
operation
50
-
+10 V DC
53
6-1*
Reference
54
6-2*
Feedback
55
-
Description
24 V DC supply
voltage for digital
inputs and external
4
transducers. Maximum
output current 200
mA
(130 mA for FC 301)
for all 24 V loads.
Digital inputs.
For digital input or
output. Default setting
is input.
Common for digital
inputs and 0 V
potential for 24 V
supply.
Safe input. Used for
STO.
Common for analog
output.
Programmable analog
output. 0-20 mA or
4-20 mA at a
maximum of 500 Ω
10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum
Analog input. For
voltage or current.
Switches A53 and A54
select mA or V.
Common for analog
input.
17
4